Section 1: Working Space and Facilities
1. Adequacy working space and safe access provided for switch room and /or electrical facilities.
Pass
Fail
N/A
2. Entrance /exit to switch room and/or electrical facilities are free of obstruction.
Pass
Fail
N/A
3. Suitable locking facilities provided for switch room and /or electrical facilities.
Pass
Fail
N/A
4. Suitable lighting provision provided for switch room and /or electrical facilities.
Pass
Fail
N/A
5. Suitable ventilation provision provided for switch room and /or electrical facilities.
Pass
Fail
N/A
6. Suitable tools for withdrawal of fuses at fuse board provided.
Pass
Fail
N/A
7. A warning notice ‘DANGER—UNAUTHORISED ENTRY PROHIBITED’ provided at every entrance of switch room.
Pass
Fail
N/A
8. Fire barriers and other measures for protection against thermal effects are properly installed.
Pass
Fail
N/A
9. Danger notices, warning notices, schematic diagrams, instructions and similar information are correctly and adequately provided.
Pass
Fail
N/A
10. Warning notices for substations and switch rooms provided in compliance.
Pass
Fail
N/A
11. Warning notices for earthing and main bonding connections provided in compliance.
Pass
Fail
N/A
12. All switchgears, distribution boards and electrical equipment properly labelled.
Pass
Fail
N/A
Section 2: Switchboard, Main Switch and Circuit Breaker
1. An up-to-date notice of periodic inspection and testing provided at point of supply (i.e. a switchboard, a circuit breaker or a distribution board) of the installation.
Pass
Fail
N/A
2. Circuits, fuses, switches, terminals, etc. are provided with a legible and durable identification label.
Pass
Fail
N/A
3. No visible damage to impair safety.
Pass
Fail
N/A
4. Work done properly recorded in logbook.
Pass
Fail
N/A
5. An up-to-date schematic diagram displayed.
Pass
Fail
N/A
6. All accessible live parts screened with insulating plate or earthed metal.
Pass
Fail
N/A
7. All exposed conductive parts effectively earthed.
Pass
Fail
N/A
8. Earthing system effectively connected.
Pass
Fail
N/A
9. Warning notice displayed at main bonding connections.
Pass
Fail
N/A
10. All protective devices are functioned properly and correctly set.
Pass
Fail
N/A
11. Suitable interlock scheme provided to prevent parallel operation of two or more sources of supply and 4-pole incoming and interconnecting circuit breakers provided for supply to be taken from more than one source and is interconnected.
Pass
Fail
N/A
12. Electrically and mechanically interlocked 4-pole changeover device(s) where standby generator set(s) is installed.
Pass
Fail
N/A
13. The breaking capacity of all circuit breakers /interconnection devices are able to withstand the prospective fault current.
Pass
Fail
N/A
14. Protective relays have been correctly set and overcurrent protective devices suitably set for all circuits.
Pass
Fail
N/A
15. Protective type current transformers are used for protective relays.
Pass
Fail
N/A
16. A means of isolation provided for every circuit.
Pass
Fail
N/A
17. Operation of circuit breakers and main switches checked.
Pass
Fail
N/A
18. Control, indication and alarm functions checked.
Pass
Fail
N/A
19. No undersized conductor used between the main busbar and fuse/MCB’s.
Pass
Fail
N/A
20. Fuses/MCB’s matching the lowest rated conductor in the circuit.
Pass
Fail
N/A
21. Suitable cable terminations provided.
Pass
Fail
N/A
22. Cable conductors of correct phases connected.
Pass
Fail
N/A
23. Single-pole devices for protection or switching connected in phase conductors only.
Pass
Fail
N/A
Section 3: Distribution Board
1. A warning notice ‘DANGER’ provided on the front panel of every distribution board.
Pass
Fail
N/A
2. A notice of periodic testing provided at or near the main distribution board incorporating a residual current device.
Pass
Fail
N/A
3. Distribution boards securely mounted on suitable supports.
Pass
Fail
N/A
4. A suitable switch provided to control each distribution board.
Pass
Fail
N/A
5. Phase barriers for 3-phase distribution board provided, where necessary.
Yes
No
6. The breaking capacity of MCB is compliant.
Pass
Fail
N/A
7. Suitable tools for withdrawal of fuses at a fuse board provided, where necessary.
Pass
Fail
N/A
8. Circuits connected to MCB or fuse in accordance with the schematic diagram.
Pass
Fail
N/A
Section 4: Conductors, Cables and Wiring
1. No visible damage to impair safety.
Pass
Fail
N/A
2. All live conductors and their methods of insulation, in relation to design currents of circuits and to the operating currents of the protective devices, are properly selected and erected.
Pass
Fail
N/A
3. All cables, flexible cords, switches, plugs and socket outlets, accessories and equipment are found to be in good working conditions.
Pass
Fail
N/A
4. All conductors are correctly and securely connected and identified.
Pass
Fail
N/A
5. Armored cables properly terminated to metal casing or trunking by proper cable glands.
Pass
Fail
N/A
6. Cables passing through smoke lobby protected by enclosures of adequate fire rating.
Pass
Fail
N/A
7. Non-sheathed cables protected by conduit, trunking or ducting.
Pass
Fail
N/A
8. Cables and ductings adequately supported.
Pass
Fail
N/A
9. Cables at distribution board or busbar terminated with cable lugs
Pass
Fail
N/A
10. Main cables connected up with correct polarity.
Pass
Fail
N/A
11. Cables protected against mechanical damage and suitably supported.
Pass
Fail
N/A
12. All exposed metal parts including the armor effectively earthed.
Pass
Fail
N/A
Section 5: Final Circuits
1. All fuses and single pole switches connected to the phase conductors only with correct polarity.
Pass
Fail
N/A
2. Wiring for emergency lightings and fire services installation segregated from other wirings.
Pass
Fail
N/A
3. Low voltage circuits segregated from extra low voltage circuits.
Pass
Fail
N/A
4. Cables of all phases and neutral of the circuit bunched and contained in the same conduit.
Pass
Fail
N/A
5. Exposed insulated non-sheathed cables protected.
Pass
Fail
N/A
6. Wiring inside false ceiling protected by conduit/trunking or metallic sheath.
Pass
Fail
N/A
7. Socket outlets installed below 1.5m from floor being shuttered type complying with the prescribed requirements.
Pass
Fail
N/A
8. No socket outlet installed close to water tap, gas tap or cooker so as to avoid danger.
Pass
Fail
N/A
9. Floor socket outlets protected with suitable cover.
Pass
Fail
N/A
10. No 2-pin sockets installed. All socket outlets connected with protective conductors and live conductors terminated at correct terminals.
Pass
Fail
N/A
11. Radial final circuits using 5A/15A socket outlets in compliance.
Pass
Fail
N/A
12. Circuit protective conductor is formed by the enclosure and a separate protective conductor between the earthing terminal of socket outlet and its associated metal box provided.
Pass
Fail
N/A
13. Circuit protective conductor is not formed by the enclosure and a separate protective conductor to the earthing terminal of socket outlet provided.
Pass
Fail
N/A
14. Residual current device having a rated residual operating current not exceeding 30mA provided for all socket outlets.
Pass
Fail
N/A
15. Minimum sizes of protective conductors are provided as per requirement for limitation of protective conductor impedance.
Pass
Fail
N/A
16. Means of isolation provided for every fixed appliance.
Pass
Fail
N/A
17. All chokes, starters and capacitors of discharge lamps enclosed in earthed metal box(es) and suitably ventilated.
Pass
Fail
N/A
18. Phase conductors connected to the center contact of the Edison-type screw lamp holders.
Pass
Fail
N/A
19. No switches other than a switch fed from a safety source or operated by an insulation cord or rod or a push-button type of switch having an insulated button of a large surface area provided in bathrooms.
Pass
Fail
N/A
20. Shaver supply unit is compliant
Pass
Fail
N/A
21. No fixed luminaire nor fixed heater having unguarded heating elements installed within reach of a person using the bath or shower.
Pass
Fail
N/A
22. Appliances exposed to weather being splash-proof type.
Pass
Fail
N/A
23. Luminaires, switches, sockets and plugs, cable couplers installed outdoor, being splash proof type.
Pass
Fail
N/A
24. General/site lighting readily accessible to the public supplied from a safety source.
Pass
Fail
N/A
25. General/site lighting not readily accessible to the public and not supplied from a safety source, protected by RCD having a rated residual operating current not exceeding 30mA.
Pass
Fail
N/A